ROBERT L. EHRLICH, JR., Governor Ch. 613
(I) IF NOT LOCATED IN A BUILDING OPEN FOR PUBLIC USE, DOES
NOT REQUIRE REGULAR FULL-TIME ATTENDANCE OR SCHEDULED VISITATION, IF
THE LICENSEE:
1. IS RESPONSIBLE FOR THE SAFE OPERATION OF SUCH
EQUIPMENT AT ALL TIMES;
2. IS AVAILABLE TO OBSERVE THE MONITORING
EQUIPMENT OR DEVICES AND MAKE NECESSARY ADJUSTMENTS AT LEAST ONCE
EVERY 24 HOURS; AND
3. MAINTAINS A DAILY INSPECTION LOG; AND
(II) IF LOCATED IN A SCHOOL, HOSPITAL, HOTEL, RESIDENTIAL
FACILITY, OR OTHER BUILDING GENERALLY OPEN TO THE PUBLIC, IS VISITED AT
LEAST ONCE EVERY 8 HOURS THAT THE BUILDING IS OPEN FOR PUBLIC USE, IF THE
LICENSEE:
1. IS RESPONSIBLE FOR THE SAFE OPERATION OF SUCH
EQUIPMENT AT ALL TIMES;
2. IS AVAILABLE TO OBSERVE THE MONITORING
EQUIPMENT OR DEVICES AND MAKE NECESSARY ADJUSTMENTS AT LEAST ONCE
EVERY 24 HOURS; AND
3. MAINTAINS A DAILY INSPECTION LOG.
(D) A GRADE 2 STATIONARY ENGINEER LICENSEE MAY OVERSEE THE
OPERATION OF A BOILER THAT:
(1) OPERATES AT A PRESSURE OF MORE THAN 15 PSI AND CAN OPERATE
AT 300 TO 499 HORSEPOWER;
(2) IS INSPECTED IN ACCORDANCE WITH THE BOILER LAWS AND
REGULATIONS BY A SPECIAL INSPECTOR OR A DEPUTY BOILER INSPECTOR;
(3) IF NOT EQUIPPED WITH A 24-HOUR COMPUTERIZED MONITORING
SYSTEM AND AUTOMATIC CONTROLS, HAS A GRADE 2 LICENSEE IN ATTENDANCE AT
ALL TIMES THAT THE BOILER IS IN OPERATION; AND
(4) IF EQUIPPED WITH A 24-HOUR COMPUTERIZED MONITORING
SYSTEM AND AUTOMATIC CONTROLS, IS ATTENDED BY A GRADE 2 LICENSEE AS
FOLLOWS:
(I) IF NOT LOCATED IN A BUILDING OPEN FOR PUBLIC USE, DOES
NOT REQUIRE REGULAR FULL-TIME ATTENDANCE OR SCHEDULED VISITATION, IF
THE LICENSEE:
1. IS RESPONSIBLE FOR THE SAFE OPERATION OF SUCH
EQUIPMENT AT ALL TIMES;
|
|
|
|
|
|
|
|
- 3463 -
|
|
|
|
|
|
|
|
|
|
|
|
|