Montgomery County                           2831

(b)    Individual outlets with taps not over 18 inches long; or,

(c)     Infra-red lamp industrial heating appliances; and

(d)     Non-heating leads of snow and ice melting cables and mats.

Exception No. 3. Fixture Wires and Cords. Fixture wires and
cords may be of smaller size, but not less than the size specified in
Exception No. 3 of Section 240-5 (a).

See Tables 400-9 (b) and 402-4.

Exception No. 4. Outlet Devices. Outlet devices may have less
carrying capacity than the branch circuit rating, but not less than the
types and ratings specified in Section 210-21 (a-c).

Exception No. 5. Wall-mounted ovens and counter-mounted
cooking units. Each wall-mounted oven and each counter-mounted
cooking unit shall be served by an individual circuit of not less than
No. 10 wire. The branch circuit wiring for these units shall be based
on one hundred per cent of the name-plate rating of the unit.

83-56. Section 220-3 of the 1968 National Electrical Code adopted by
this Chapter is hereby amended to read as follows:

220-3. Branch circuits required. Branch circuits shall be installed
as follows:

(a) Lighting and appliance circuits. For lighting, and for ap-
pliances, including motor-operated appliances, not specifically pro-
vided for in Section 220-3(b), branch circuits shall be provided for a
computed load not less than that determined by Section 220-2.

The number of circuits shall be not less than that determined
from the total computed load and the capacity of circuits to be used.
In every case the number shall be sufficient for the actual load to be
served, and the branch circuit loads shall not exceed the maximum
loads specified in Section 210-23.

Where the load is computed on a "watts per square foot" basis,
the total load, insofar as practical, shall be evenly proportioned
among the branch circuits according to their capacity.

General lighting branch circuits in dwellings, as well as other
occupancies, shall supply not more than twelve outlets.

When lighting units to be installed operate at other than 100 per
cent power factor, see Section 210-23(b) for maximum ampere load
permitted on branch circuits.

For general illumination in dwelling occupancies, it is recom-
mended that not less than one branch circuit be installed for each 500
square feet of floor area in addition to the receptacle circuits called
for in Section 220-3(b).

 

clear space
clear space
white space

Please view image to verify text. To report an error, please contact us.
Session Laws, 1972
Volume 708, Page 2831   View pdf image
 Jump to  
  << PREVIOUS  NEXT >>


This web site is presented for reference purposes under the doctrine of fair use. When this material is used, in whole or in part, proper citation and credit must be attributed to the Maryland State Archives. PLEASE NOTE: The site may contain material from other sources which may be under copyright. Rights assessment, and full originating source citation, is the responsibility of the user.


Tell Us What You Think About the Maryland State Archives Website!



An Archives of Maryland electronic publication.
For information contact mdlegal@mdarchives.state.md.us.

©Copyright  August 17, 2024
Maryland State Archives